Save Energy in your Supermarket with a CO2 Refrigeration System

15 September 2011 | Author: Ejnar Luckmann, Kenneth Bank Madsen & Carsten Glud Andersen
Benchmarking energy optimised HFC stores with transcritical CO2 booster systems

The Danish Supermarket Chain, Fakta – owned by Coop Denmark has experienced significant energy savings with their second generation transcritical booster system.
Fakta saves 10% energy by applying a CO2 system compared to HFC systems.
Average user rating:
out of votes
> Click here to read the full article
Chapter 1. Fakta
Fakta has continuously worked on lowering their energy consumption for the past 15 years, first on their HFC scroll packs and later on transcritical packs. As a result of this Fakta are now installing their second generation transcritical packs where part load has been optimized. Fakta and the remote monitoring centre AK Centralen has been collecting data from the systems for more than 15 years, where they started optimizing the HFC pack with low energy consumption and temperature quality as main targets. 

The Fakta chain has 378 stores in operation where 61 of them are transcritical. Fakta was one of the first movers to change to CO2 and the first generation of transcritical systems were installed in 2007. The aim for 2011 is to install more than 40 systems which are relatively small with 9 kW on LT and 28 kW on MT.

Today all systems are produced in batches of 5 packs as they are standardised with the same configuration regarding capacity. The installation can be different but cabinets, pack and gascooler, are always the same arrangement. This makes Fakta a very good reference for energy studies.
Chapter 2. System Design (click to open)
HFC System
  • Parallel R404a system with very good loadadaptation,
  • Controlled by ADAP-KOOL® pack controllerand AKC 114A case controllers with electronicexpansion valve type AKV
  • 148 systems in operation
  • 10 selected for the study.
Transcritical 1st Generation System
  • Booster system with gas by pass.
  • 2 compressors for MT (33/67%) and 2 for LT(33/67%
  • Mechanical gas by pass valve
  • Controlled by ADAP-KOOL® pack controller,EKC 326 controlling ICMTS high pressure valve,and AK-CC 750 case controllers with electronicexpansion valve type AKV
  • 32 systems in operation
  • First10 selected for the study.
Transcritical 2nd Generation System
  • Booster system with gas by pass
  • 2 compressors, one with AKD inverter for MTand 2 compressors without inverter for LT
  • Controlled by ADAP-KOOL® pack controller,EKC 326A controlling ICMTS high pressurevalve and CCM stepper gas by pass valve, andAK-CC 750 case controllers with electronicexpansion valve type AKV
  • 10 systems in operation May 2010 and 29 inDecember 2010
  • First 10 selected for the study.

Chapter 3. Selection Criteria for Energy Study (click to open)
For the installation to be included in the data material the following criteria had to be fulfilled:
  • More than 4 months of operation since commissioning
  • Equivalent size and opening hours
10 installations have been selected from each system. The stores are identical on most parameters, but the installation will of course be different regarding length of pipes and number of bends.

The maximum pressure drop in the pipe work is still the same for all systems regardless of refrigerant
and installation.
Chapter 4. Results (click to open)


The energy data in this study is collected from May 2010 to April 2011. The plot shows energy consumption per month for the 3 different systems (HFC, Trans 1 and Trans 2) and the average
ambient temperature for the month.

Application Engineer Kenneth B. Madsen from Danfoss explains “Our measurements indicates approximately 10% energy savings in Denmark when comparing the 2nd generation transcritical CO2 system with the HFC system - with the lowest energy consumption in the cold months” and further “The results also show a technology improvement since 2007 where the first generation transcritical system was installed."
Chapter 5. Conclusion (click to open)
The results show that the 2nd generation transcritical systems in Fakta consume approximately
10% less energy than the HFC packs installed until 2007. Energy simulations indicate that the
energy consumption in Denmark should be approx 10% lower than HFC systems which are very
much in line with the test results.

The difference in energy consumption between the 1st and 2nd generation CO2 transcritical systems can be explained by improved part load capabilities and smooth control of gas bypass as well as availability of components in smaller sizes to be able to better match the capacity also for smaller systems.

And a new CO2 injection algorithm in AK-CC 750.

ADAP-KOOL® - "Solutions you can grow with"